Permit #B1900393
Address3101 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderARMINCO INC.
Owner3101 WILSON LLC % THE JOHN AKRIDGE COMPANIES
Applied Date02/13/2019
Approved Date04/05/2019
Date Issued04/08/2019
DescriptionNEW TENANT LAY OUT FOR 1ST FLOOR UNIT 0003 FOR **FORMULA RUNNING CENTER**

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewBuilding
Review Date02/21/2019
StatusRejected
Comments
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plans Examiner for any clarification of the comments.
Permit #:    B1900393    Applicable Code:    VUSBC 2012 Edition
Project Name :        Plans Examiner:    Mohamed Ghiwane
Address:    3101 Wilson Blvd    Discipline:     Building
Review Date:    02/21/19    Phone Number:    703-228-0578
Review #:    1st    Fax Number:    703-228-7046
Revision Date:    NA    Email:    mghiwane@arlingtonva.us
            
    Sheet    Comments    Code Reference
1.    A1.0    An accessible family or assisted-use bathing room shall be provided    Section 1109.2.1
2.    A1.0    Doors 114 and 105 at men and women's accessible toilet compartment shall not swing into the required minimum area of the compartment.     Section 604.9.3 of the 2009 ICC A117.1
3.    A1.0    Transfer type shower must be exactly 36" wide and 36" deep.     Section 608.2.1.1 of the 2009 ICC A117.1
4.    A1.0    A clearance of 48" minimum in length measured perpendicular from the control wall shall be provided. Please note that forward approach is not permitted in this case.    Section 608.2.1.2 of the 2009 ICC A117.1
5.    C-0    Occupant load at locker rooms shall be calculated at 50 SF/Occp. Please revise.    Table 1004.1.2
6.    A1.0    Please clarify what is the use of VO2 Max 104 and CRYO 115 rooms. Also, please specify the occupant load factor used for each room.    
7.    A1.0    It appears to be that the partition at men's accessible toilet compartment extends all the way to the floor. In this case the accessible toilet compartment shall be 66" x 62" if wall-hung water closet or 66"x 65" if floor mounted water closet is used.     Section 604.9.2 of the 2009 ICC A117.1.
8.    A1.0    Infrared Sauna 114 must be accessible. Please provide a clear floor space complying with Section 304.3 of the 2009 A117.1.    Section 1109.6
9.    A1.0    Please provide elevation details for the reception desk and show compliance with Section 904 of the 2009 ICC A117.1.    
10.    A1.0    A bench complying with Section 903 of the 2009 ICC A117.1 is required at both locker rooms.    Section 803.4 of the 2009 ICC A117.1.
11.        More comments can be generated during next review.    
  



  
 